BUY New & Used Commercial Backup Generators 1900kW-1999kW GENERATORS FOR SALE
A requirement between 1900 kW and 1999 kW sits 1 to 100 kW short of 2000 kW, a size we list far more often than anything inside this band, so the real decision here is whether to buy exactly what the load study says or step up to a 2000 kW set. Below are the spec sheets on either side of the band, the fuel and current figures for that last 100 kW, and the rating and supply questions that usually settle it.
Not finding what you’re looking for? Let us help!
GENERATOR SERVICE & REPAIR
Keep your equipment running peak performance with preventive maintenance and repair.
Subscribe For Inventory Updates
We promise not to blow up your
inbox!
Industries That Use 1900 kW to 1999 kW Generators
A load study that lands in the 1,900s usually comes from a facility that has already counted every building, line, and motor it must keep running. The buyers below tend to arrive with a number, not a guess, and the open question is whether to buy right at it or round up.
- Data centers: Enterprise halls that have outgrown a 1500 kW frame but don’t need a paralleled plant, where the critical load plus cooling comes in just below 2 MW.
- Hospitals: Campus expansions where a new wing pushes an existing essential load past what the old set carried, and the replacement has to cover the whole list at once.
- Water districts: Treatment plants and large pump stations, where several big motors set the figure and the margin above them is what keeps a pump start from tripping the rest.
- Universities and campuses: Central plants serving a cluster of buildings from a single machine, sized zone by zone until the total sits under 2,000 kW.
- Airports: Terminal and airfield loads with backup written into regulation, where the set has to carry everything on the essential bus together.
- Oil and gas processing: Plant and field sites with long-hour duty, the one place in this band where the prime or continuous rating matters more than standby.
- Heavy manufacturing: Plants with large compressors, presses, or chillers, where the starting step of the biggest motor pushes a 1,700 kW running load toward 2 MW.
Sector-by-sector sizing guidance lives on our industries served pages.
1900 kW to 1999 kW Generators at a Glance
- Apparent power: 2,375 to 2,499 kVA at 0.8 power factor.
- Current at 480V: our chart has no row in this band; it lists 2,640 A at 1750 kW and 3,015 A at 2000 kW, and the calculated figure is about 2,857 A at 1900 kW and 3,006 A at 1999 kW.
- Diesel burn at full load: between the chart’s 124.2 gal/hr at 1750 kW and 141.9 gal/hr at 2000 kW.
- Weight on either side: 28,443 lb wet for an open Kohler KD1500 just below the band, 47,523 lb for an open mtu DS2000 just above it.
- Supply: nothing listed inside the band right now, against nine units listed at exactly 2000 kW.
- What decides it: your average load against the rating you buy, and whether the last 100 kW is worth the extra current and fuel.
Nothing Listed Between 1900 kW and 1999 kW Right Now
The inventory panel above shows no units in this band today. That isn’t unusual: large standby sets tend to be built at round outputs, and what we list clusters at 1500 kW and 2000 kW rather than in between. The nearest stock is just above the band, on our 2000 kW generators page:
| Model | Output | Condition |
|---|---|---|
| Cummins DQKAB | 2000 kW | Used, two units at 150 hours, 2007; and new, 2025 |
| Caterpillar 3516C | 2000 kW | Used, 170 hours, 2015 |
| Kohler 2000REOZMD | 2000 kW | Used, 361 hours, 2012 |
| Baldor IDLC2000-2M power module | 2000 kW | Used, 491 and 645 hours, 2010 |
| Cummins C2000D6E | 2000 kW | New, two units, 2026 |
Every one of those is a Tier 2 diesel, and none of the used sets has reached 650 hours. Just below the band, the 1500 kW generators page carries used Cummins DQGAB, Caterpillar 3512C, and Detroit Diesel / MTU 1500DSEB sets. For everything below 2 MW in one view, see the 1500kW – 1999kW range.
The Spec Sheets That Bracket the Band
No sheet we work from is rated inside 1900 to 1999 kW, so these four show what sits on each side of it:
| Model | Fuel | Published rating | Position against this band | Fuel figure |
|---|---|---|---|---|
| Kohler KD1500 | Diesel | 1500 kW standby, 1350 kW prime at 480V | 400 to 499 kW below | 58.6 gal/hr at half, 105.9 at full |
| Caterpillar G3516C | Natural gas | 1660 ekW continuous | 240 to 339 kW below | 9,480 Btu/ekW-hr at full load |
| Jenbacher J612 | Natural gas | Up to 2,078 kW at 60 Hz | Its top rating clears the band | Up to 45.2% electrical efficiency |
| mtu 16V4000 DS2000 | Diesel | 2000 kW standby | 1 to 100 kW above | 74 gal/hr at half, 106 at 3/4, 143 at full |
The Jenbacher J612 is the only sheet here whose range reaches past 1999 kW without being a 2000 kW diesel. It’s offered from 480V up to 13.8kV, and Jenbacher notes its data depends on gas quality and ambient conditions, so get flow and inlet pressure from the sheet for the specific engine you are quoted. For emergency standby the practical comparison is the two diesels: going from the KD1500 to the DS2000 raises full-load burn by about 37 gal/hr and current at 480V from 2,256 A to 3,007 A on the makers’ own sheets.
Fuel Rows at 1750 kW and 2000 kW
Our diesel fuel consumption chart steps in 250 kW increments and has no 1900 kW row. A set in this band burns somewhere between these two lines:
| Size | 1/4 load | 1/2 load | 3/4 load | Full load |
|---|---|---|---|---|
| 1750 kW | 37.5 gal/hr | 63.2 gal/hr | 90.7 gal/hr | 124.2 gal/hr |
| 2000 kW | 42.8 gal/hr | 72.2 gal/hr | 103.5 gal/hr | 141.9 gal/hr |
The gap between the two rows at full load is 17.7 gal/hr. Over 24 hours, that is about 2,981 gallons at 1750 kW against about 3,406 gallons at 2000 kW, so a set in the 1,900s needs a tank sized near the upper figure for the same runtime. mtu’s sheet for the DS2000 lists 143 gal/hr at full standby load, within about a gallon of the chart’s 2000 kW row, and names #2 diesel or HVO as the recommended fuel.
What matters more than nameplate burn is what the set burns at your actual load. A 2000 kW set carrying 1,900 kW is running at 95% of its rating, and the chart and sheets put its consumption close to the full-load figure, not the 3/4 one.
Amps at 480V, 600V, and 4160V Around 1900 kW
The two nearest rows on our generator amperage chart, three-phase at 0.8 power factor, with the band’s endpoints calculated from kVA because the chart has no row for them:
| Output | kVA | 480V | 600V | 4160V |
|---|---|---|---|---|
| 1750 kW (chart) | 2,188 kVA | 2,640 A | 2,106 A | 304 A |
| 1900 kW (calculated) | 2,375 kVA | about 2,857 A | about 2,285 A | about 330 A |
| 1999 kW (calculated) | 2,499 kVA | about 3,006 A | about 2,404 A | about 347 A |
| 2000 kW (chart) | 2,500 kVA | 3,015 A | 2,405 A | 348 A |
The chart marks 208V and 220V unavailable at both rows, so 480V is the lowest practical voltage here. Moving from 1900 kW to 2000 kW adds roughly 158 A at 480V but only about 18 A at 4160V, which is why the step up is an easy decision on a medium-voltage site and a harder one on a low-voltage switchboard that was laid out around the smaller figure. mtu’s DS2000 sheet gives 3,007 A at 480V and 347 A at 4,160V, in line with the chart. Our power calculators will turn your load list into a current figure at your own voltage.
Is the Last 100 kW Worth Crossing 2 MW For?
Usually yes, unless your switchgear, fuel system, or pad was designed around the smaller set.
Buy inside 1900 to 1999 kW when you are replacing a set of that size into an existing installation and the breaker, cable, tank, and pad are already built for it, or when a spec or permit names the output. In that case matching what is there is cheaper than re-engineering around 2000 kW. Step up when the installation is new or being rebuilt anyway, when the load study has no margin left once the largest motor start is included, or when you want the wider choice of new and used units that 2000 kW offers. Altitude and sustained heat both cut available output, so a site that is hot or high should be checked against the derated figure before you settle on a number in the 1,900s.
Standby Headroom: Average Load Against the Rating
If your facility runs near 1,900 kW for long stretches, a 2000 kW standby rating may not cover it, so compare on prime or continuous ratings instead.
Standby ratings come with conditions. mtu limits the DS2000’s standby rating to an average output of no more than 85% across a 24-hour period and allows no overload, which caps the average at 1,700 kW on a 2000 kW set. A load that averages in the 1,900s during an extended outage sits above that line even though it is under the nameplate. Kohler’s KD1500 sheet shows the same gap from the other side of the band: its prime figure at 480V is 150 kW under its 1500 kW standby rating. Ask for the prime or continuous figure on any set you consider here, and size against that if the generator will carry load for days rather than hours. Diesel units are under industrial diesel generators and sets built for fixed backup duty under industrial standby generators.
Why a 2000 kW Set Is Often the Easier Buy
Because that is where the supply is, new and used.
We have nine units listed at exactly 2000 kW from four makers, including used sets with 150 to 645 hours and new Cummins C2000D6E and DQKAB units, while nothing is listed inside this band. Hold out for 1,950 kW and you are choosing from whatever turns up. Accept 2000 kW and you can usually weigh a low-hour used frame against new stock. The trade is fuel and current: the chart’s full-load row climbs 17.7 gal/hr from 1750 kW to 2000 kW, and a 2000 kW set carries roughly 158 A more at 480V than a 1900 kW one, which matters only if the installation can’t absorb it. If cost is the obstacle, our generator financing options spread the purchase, and our rental side, Stag Power Rentals, can bridge the gap while the permanent set is sourced.
Running a Larger Set Below Its Rating
A 2000 kW set at partial load burns about what a smaller set burns at full load, so stepping up costs little in fuel when your load sits well below 2 MW.
The makers’ sheets show it directly. mtu lists the DS2000 at 106 gal/hr at 75% of its standby rating, or 1,500 kW, while Kohler lists the KD1500 at 105.9 gal/hr carrying the same 1,500 kW at full load. At half load the DS2000 burns 74 gal/hr. The caution runs the other way: a diesel that spends long periods lightly loaded can build up unburned fuel in the exhaust, so a 2000 kW set bought for a 1,200 kW load is a different problem from one bought for 1,950. Exercise it under real load or with load bank testing on a schedule.
Neighboring Bands to 1900 kW to 1999 kW
This band is only 100 kW wide, so check the ranges on both sides before you commit.
| Range | kVA | When it fits better |
|---|---|---|
| 1700kW – 1899kW | 2,125 to 2,374 kVA | The load study and largest motor start both come in under 1,900 kW |
| 1900kW – 1999kW (this range) | 2,375 to 2,499 kVA | Replacing a like-size set, or a spec that names the output |
| 2000kW – 2299kW | 2,500 to 2,874 kVA | New installations, thin margins, or a need for the wider 2000 kW supply |
| 1500kW – 1999kW | 1,875 to 2,499 kVA | Comparing every size below 2 MW in one place |
Every output we carry is also on shop by kW.
Inspected, Load Tested, and Backed After the Sale
Before any set ships from our yard it passes a 22-point inspection and load bank testing, and in a band this close to 2 MW that test is the proof a unit holds the output you are paying for. Turnkey Industries has bought and sold industrial generators for more than ten years. New or used, the unit comes with our 30-day IronClad warranty, and after commissioning our technicians handle industrial generator repair, routine maintenance, and emergency service. How freight is handled is covered in our shipping and returns policy.
Ready to Buy a 1900kW – 1999kW Generator?
Tell us your load study figure, your service voltage, and whether the generator replaces an existing set or goes into a new installation. We’ll say plainly whether to buy in the 1,900s or move to 2000 kW, and list the units that fit. Compare our used industrial generators with our new industrial generators, or contact us to go over the numbers together.
1900kW – 1999kW Questions: Stepping Up, Headroom, and the 2 MW Mark
Should I buy a 1950 kW generator or a 2000 kW generator?
For a new installation, 2000 kW is usually the better buy, because supply is much wider at that size and the extra fuel and current are modest. Stay in the 1,900s when an existing breaker, cable, tank, or pad was built around that output.
How many amps does a 1900 kW to 1999 kW generator draw at 480V?
About 2,857 A at 1900 kW and 3,006 A at 1999 kW, calculated from kVA at 0.8 power factor. Our amperage chart has no row in the band; it lists 2,640 A at 1750 kW and 3,015 A at 2000 kW.
How much diesel does a generator in this band burn?
Between 124.2 and 141.9 gal/hr at full load, the chart’s 1750 kW and 2000 kW rows. Over 24 hours that is between about 2,981 and 3,406 gallons.
Can a 2000 kW standby set carry a 1,900 kW load around the clock?
Not on a standby rating that caps average output. On the DS2000, mtu holds the 24-hour average under standby to 85%, or 1,700 kW, so a long-duration load in the 1,900s calls for a prime or continuous rating.
Why are there so few units listed in this band?
Large standby sets are mostly built at round outputs, and what we list clusters at 1500 kW and 2000 kW. Nothing is listed between 1900 and 1999 kW right now, while nine units are listed at 2000 kW.
Is there a natural gas option near 1900 kW?
Yes. The Jenbacher J612 is rated up to 2,078 kW at 60 Hz, with electrical efficiency of up to 45.2%. Confirm gas supply against the specific unit’s sheet; for emergency standby, diesel is still the usual choice.
Does a medium-voltage site change the decision?
It makes stepping up easier. At 4160V the move from 1900 kW to 2000 kW adds only about 18 A, against roughly 158 A at 480V.