Between 500 kW and 999 kW, a generator can be a pad-mount standby set or a containerized power module on its own chassis, and that choice changes weight, fuel, noise, and hours as much as the kW figure does. This is also where many data center buyers start sizing, and where a gas set’s LP rating can fall well below its natural gas nameplate.
Not finding what you’re looking for? Let us help!
GENERATOR SERVICE & REPAIR
Keep your equipment running peak performance with preventive maintenance and repair.
Subscribe For Inventory Updates
We promise not to blow up your
inbox!
Industries That Use 500 kW to 999 kW Generators
Here one generator often carries a whole facility, and a self-contained power module on a chassis competes with a set bolted to a pad. Who buys depends on which format the job calls for.
- Data centers: Edge sites, smaller colocation facilities, and single-building IT rooms often start sizing at 500 kW.
- Hospitals: Multi-wing facilities that keep the whole building live on a pad-mount standby set.
- Campuses: Around 600 kW, one set can realistically anchor a cluster of connected buildings that share electrical infrastructure.
- Manufacturing and processing: Plants restarting several large motors, pumps, and fans on one service.
- Rental fleets: The main buyers of containerized power modules and large towables.
- Construction and events: Large sites and temporary installations on trailer units.
- Mining and oil and gas: Remote and off-grid sites where an 800 kW class set is the only power, specified on its prime rating with extended fuel storage.
- Cities and municipalities: Neighborhood-level emergency response and early microgrid projects, where a 750 kW set acts as a temporary utility for a cluster of buildings.
Sizing notes by sector are on our industries served pages.
500 kW to 999 kW Generators at a Glance
- Apparent power: 625 to 1,249 kVA at 0.8 power factor.
- Current: 752 A at 500 kW to 1,354 A at 900 kW at 480V, or 87 to 156 A at 4160V. At 208V the same span runs 1,735 to 3,120 A.
- Diesel burn at full load: 35.7 gal/hr at 500 kW, 42.8 at 600 kW, and 53.4 at 750 kW on our chart.
- Weight: about 10,500 lb for an open Generac SD750 to 22,496 lb for an open Generac SD800. A containerized Cat XQ500 is 27,595 lb with full fuel, plus a 7,450 lb chassis.
- Two common formats: pad-mount diesel standby, many listed as EPA Tier 2, and trailer-mounted units or power modules for rental and temporary duty.
- Decision driver: format and fuel first. A container on a chassis, a sound-enclosed pad set, and a dual-fuel gas set are priced and permitted on different terms.
Narrowing 500 kW to 999 kW Into Three Bands
Most buyers land in one of these once the load list is totaled.
| Band | kVA | What drives it |
|---|---|---|
| 500kW – 669kW | 625 to 836 kVA | The data center entry point and the busiest band for mobile power. Most of the trailer units and power modules we list sit here, alongside 500 kW and 600 kW standby sets. |
| 670kW – 839kW | 838 to 1,049 kVA | 700, 750, and 800 kW standby sets for plants and campuses, plus 795 to 800 kW power modules for remote and off-grid work. |
| 840kW – 999kW | 1,050 to 1,249 kVA | Pad-mount standby and natural gas sets just under a megawatt, where buyers weigh one more unit here against a single larger frame. |
For a single size, see our 500 kW, 600 kW, 750 kW, and 800 kW generator pages.
Trailers, Power Modules, and Standby Sets in Our Yard
Units in this range that we’ve listed, at the kW we listed them:
| Model | Output | Format | Condition |
|---|---|---|---|
| Cummins DFEK, Tier 2 | 500 kW | Standby | New, and used at 500 hours |
| Caterpillar C15, Tier 2 | 500 kW | Standby | Used, 276 hours |
| Generac 500 kW diesel | 500 kW | Standby | Used, 446 hours |
| Cummins GFJC and GTA28 | 500 kW | Natural gas standby | Used, 200 and 781 hours |
| Gillette SP-5000 | 500 kW | Natural gas standby | New |
| Wanco WSP690 | 500 kW | Trailer | New |
| Atlas Copco QAS600 and QAS700VD | 503 kW and 560 kW | Trailer | Used, 2,317 and 20 hours |
| Multiquip DCA600SSV, Tier 2 | 528 kW | Trailer | Used, 9,595 hours |
| Hipower HRVW625 and HRVW685 | 550 kW and 605 kW | Trailer | Used, 1,133 and 3,209 hours |
| Caterpillar XQ600 | 567 kW | Power module | Used, 6,368 and 10,692 hours |
| Kohler 600REOZV, Tier 2 | 600 kW | Standby | Used, 630 hours |
| Cummins DQCA and DFGB; Caterpillar C18 | 600 kW | Standby | Used, 297 to 747 hours |
| Cummins GTA38 | 600 kW | Natural gas standby | Used, 264 hours |
| Caterpillar 3412C | 700 kW | Standby | Used, 583 hours |
| Cummins DQCB and DQFAA, Tier 2 | 750 kW | Standby | Used, 420 to 792 hours |
| Caterpillar XQ800 | 795 kW | Power module | Used, 4,785 hours |
| Kohler 800REOZMB | 800 kW | Standby | Used, 528 and 1,711 hours |
| Cummins DFHB QST30-G2 and Caterpillar 3508 | 800 kW | Power module | Used, 8,276 and 11,147 hours |
| Cummins 880GFLC | 880 kW | Natural gas standby | Used, 660 hours |
| Cummins DQFAC, Tier 2 | 900 kW | Standby | Used, 502 hours |
The hours split cleanly by format. Every used pad-mount standby set above has under 1,750 hours, most under 800, while the used power modules run from 4,785 to 11,147 hours, which fits a life of rental and prime duty. Whatever is on the ground today is in the listings above.
Published Specs for Five Models From 500 kW to 800 kW
Manufacturer figures for a container module, pad-mount diesels, and gas sets:
| Model | Fuel and format | Standby / prime | Full-load fuel | Weight or supply |
|---|---|---|---|---|
| Caterpillar XQ500 | Diesel, 20 ft container module, Tier 4 Interim | 500 kW / 455 kW | 35.9 gal/hr | 22,590 lb empty tank, 27,595 lb full |
| Kohler 500REZXD | Natural gas, LP backup, stationary | 500 kW on gas, 295 kW on LP | 5,888 cfh | 7.0 to 11.0 in. H2O at the inlet |
| Kohler 600REOZVB | Diesel, stationary, Tier 2 | 600 kW / 555 kW | 42.7 gph | 10,770 lb wet, open |
| Generac SG750 | Natural gas, stationary | 750 kW standby | 8,370 scfh | 14,824 to 16,967 lb, open |
| Generac SD800 | Diesel, stationary, Tier 2 | 800 kW / 720 kW | 74.4 gal/hr | 22,496 lb, open |
Two things stand out. The XQ500 is the only Tier 4 Interim unit here, while the pad-mount diesels are Tier 2 for stationary emergency use, and each certification limits where and how a unit can run. And the Kohler 500REZXD is a reminder that a dual-fuel nameplate describes natural gas only. On LP it makes 295 kW, about 59% of its gas rating, so a site counting on LP backup has to size to the lower number.
Diesel Burn From 500 kW to 1000 kW on Our Chart
Our diesel fuel consumption chart has three rows inside this band and none at 800 or 900 kW, so the 1000 kW row brackets the top:
| Size | 1/4 load | 1/2 load | 3/4 load | Full load |
|---|---|---|---|---|
| 500 kW | 11.0 gal/hr | 18.5 gal/hr | 26.4 gal/hr | 35.7 gal/hr |
| 600 kW | 13.2 gal/hr | 22.0 gal/hr | 31.5 gal/hr | 42.8 gal/hr |
| 750 kW | 16.3 gal/hr | 27.4 gal/hr | 39.3 gal/hr | 53.4 gal/hr |
| 1000 kW | 21.6 gal/hr | 36.4 gal/hr | 52.1 gal/hr | 71.1 gal/hr |
At 500 kW and 600 kW the sheets land almost on the chart: Cat lists 35.9 gal/hr for the XQ500 and Kohler 42.7 gph for the 600REOZVB. Generac’s SD750 comes in under it at every step, at 14.3, 25.6, 38.0, and 49.7 gal/hr. The SD800 goes the other way, listing 74.4 gal/hr at full standby, more than the chart’s 1000 kW row.
At full load a 500 kW set burns about 857 gallons in 24 hours and a 750 kW set about 1,282. The XQ500 carries a 700-gallon double-wall tank that Cat rates for 24 hours at 75% of prime plus 10%. Pad-mount tanks vary more: the SD750’s sub-base tanks run 334 gallons (6 hours) to 2,002 gallons (40 hours), and Kohler lists a 3,052-gallon tank for the 600REOZVB where state code calls for 72 hours.
Current at 208V Through 4160V Across the Band
Three-phase current at 0.8 power factor, from our generator amperage chart:
| Output | kVA | 208V | 480V | 600V | 4160V |
|---|---|---|---|---|---|
| 500 kW | 625 kVA | 1,735 A | 752 A | 602 A | 87 A |
| 600 kW | 750 kVA | 2,080 A | 902 A | 721 A | 104 A |
| 700 kW | 875 kVA | 2,430 A | 1,052 A | 842 A | 121 A |
| 800 kW | 1,000 kVA | 2,780 A | 1,203 A | 962 A | 139 A |
| 900 kW | 1,125 kVA | 3,120 A | 1,354 A | 1,082 A | 156 A |
At 208V, current passes 1,700 A at the bottom of the band and 3,000 A near the top, so 480V is the working voltage for most of this range. Generac’s sheets list 1,129 A at 480V for its 750 kW sets and 1,203 A for the SD800. A towable or module has to match the site’s voltage at the connection point. Our power calculators will check the load total first.
Power Module on a Chassis or Pad-Mount Standby Set?
A power module suits temporary, rental, or multi-site duty; a pad-mount set suits permanent standby at one address.
Cat’s XQ500 puts the set in a 20 ft ISO high cube container on a 2-axle chassis with anti-lock brakes, with its own tank, silencer, and enclosure, rated 72 dB(A) at 7 m with 110% spill containment for engine fluids. On the chassis it measures 240 x 96 x 150 inches. That clears the 102-inch federal width standard, and at 12.5 ft it sits under the 13.6 to 14.6 ft range of state height limits FHWA reports, but each move still needs a route and permit check.
A pad-mount set is bought by the piece: Kohler’s 600REOZVB weighs 10,770 lb wet as an open set, and its housing choices run from 91 dB(A) in a steel weather enclosure to 76 dB(A) in a steel sound enclosure. Adding the 541-gallon sub-base tank takes the steel sound package to 17,003 lb, which ships assembled with lift lugs for a crane and spreader bar. Units on running gear are under trailer-mounted generators and permanent sets under industrial standby generators.
Is 500 kW Where a Data Center Starts?
For edge sites, smaller colocation facilities, and single-building IT loads, often yes.
Operators commonly begin sizing at 500 kW, then scale up with paralleled units as the facility grows. What matters most here is transfer speed: the switchover has to happen within seconds to avoid interrupting servers, which favors diesel. Pad-mount Tier 2 standby sets such as the Cummins DFEK and Caterpillar C15 we’ve listed at 500 kW fit that role, and a rental module like Cat’s XQ500 can carry a site while a permanent set is installed or replaced.
What Happens to the Rating on Natural Gas or LP?
Natural gas usually holds the standby rating if the gas service can deliver the flow; LP can cut it sharply.
Gas sets in this band are rated against a specific supply. Kohler’s 500REZXD needs 7.0 to 11.0 in. H2O at the inlet and draws 5,888 cfh at full load. Cummins’ C600N6 draws 9,557 cfh at full load on 14 to 20 in. WC, and Generac’s SG750 needs 8,370 scfh on 14 to 20 inches of water column. If the service can’t hold that pressure and flow, the set won’t make its nameplate. LP as a backup fuel is the bigger limit: the 500REZXD drops from 500 kW to 295 kW when it switches over. Gas units we list, up to the 880 kW Cummins 880GFLC, are under industrial natural gas generators, with diesel sets under industrial diesel generators.
Standby or Prime, and What Used Looks Like Here
Compare the rating that matches your duty: standby for outage backup, prime for long runs or off-grid power.
Most sheets in this band publish both, about 7% to 10% apart: 500 and 455 kW on the XQ500, 600 and 555 kW on the 600REOZVB, 800 and 720 kW on the SD800. Generac does not offer the SD750’s 675 kW prime rating in the U.S. at all. On used equipment, format predicts hours, as the yard table shows. New is the answer when a spec requires a factory warranty, a current emissions tier, or new equipment outright. Browse used industrial generators and new industrial generators side by side.
Rent the Module or Own the Set?
Rent a module for turnarounds, construction phases, events, or bridging a failed unit; own the set when it protects a facility permanently.
A standby set runs a few hours a year on a permanent pad and fuel system. Our rental side, Stag Power Rentals, handles short-term work, and our generator financing options help when budget timing is the obstacle.
Below 500 kW or Above 999 kW: The Neighboring Ranges
A diesel set run lightly loaded for long stretches develops wet stacking, so oversizing costs more than the purchase.
| Range | kVA | What it usually powers |
|---|---|---|
| 100kW – 499kW | 125 to 624 kVA | Facility standby, production floors, cold storage, mid-size commercial |
| 500kW – 999kW (this range) | 625 to 1,249 kVA | Edge and colocation data centers, hospitals, campuses, plants, rental power modules |
| 1000kW – 1499kW | 1,250 to 1,874 kVA | Healthcare campuses, enterprise data centers, processing plants, mines |
If the load sits right at 500 kW with little motor start, compare our 400 kW generators. If it runs past 999 kW, the next step is our 1000 kW generators. You can also browse every output we carry on shop by kW.
Inspected, Load Tested, and Backed After the Sale
Every generator we sell goes through a 22-point inspection and load bank testing before it ships, which matters most on high-hour power modules coming off rental duty. We’ve been buying and selling industrial generators for over a decade. Each purchase carries our 30-day IronClad warranty, and our service and maintenance team covers scheduled testing, industrial generator repair, and emergency service after delivery.
Ready to Buy a 500kW – 999kW Generator?
Tell us your load, voltage, fuel, and whether the unit stays on one pad or moves between sites, and we’ll match it to a standby set or a power module. Look through our used industrial generators and new industrial generators, or contact us and we’ll work the sizing with you.
500kW – 999kW Questions: Containers, Gas Ratings, and Data Centers
How much diesel does a generator in this range use in a day?
About 857 gallons in 24 hours for a 500 kW set at full load and about 1,282 gallons for a 750 kW set, based on our diesel chart. At 3/4 load a 500 kW set uses about 634 gallons.
Can a containerized power module travel on the highway?
Usually, with a route check. Cat’s XQ500 is 96 inches wide and 150 inches tall on its chassis, inside the 102-inch federal width standard and under the state height limits FHWA reports.
Does a natural gas generator keep its rating on LP?
Not always. Kohler’s 500REZXD makes 500 kW on natural gas but 295 kW on LP vapor, so a site relying on LP backup should size to the lower figure.
Is 500 kW enough for a data center?
For edge sites, smaller colocation facilities, and single-building IT loads, it is a common starting point. Larger facilities scale up from there with paralleled units, and transfer speed matters as much as capacity.
Why do used power modules have so many more hours than standby sets?
Modules work rental and prime duty; standby sets run for testing and outages. In our listings, used modules run 4,785 to 11,147 hours and used standby sets mostly under 800.
How long will a sub-base tank run a set this size?
It depends on the tank. Generac’s SD750 tanks run 6 hours at 334 gallons to 40 hours at 2,002 gallons, and Kohler offers a 3,052-gallon tank on the 600REOZVB for 72-hour state code requirements.